python Modbus 进行通讯时抛出Modbus Error: Exception code = 2

2023-02-21,,

源码:

import modbus_tk
from modbus_tk import modbus_tcp
import modbus_tk.defines as cst PORT = 'com1' def main():
"""main"""
logger = modbus_tk.utils.create_logger(name="console", record_format="%(message)s")
# Create the server
server = modbus_tcp.TcpServer(address="127.0.0.1", port=502)
try:
logger.info("running...")
logger.info("enter 'quit' for closing the server")
server.start()
slave_1 = server.add_slave(1)
slave_1.add_block('0', cst.HOLDING_REGISTERS, 0, 4)
slave_1.set_values('0', 0, [1,2,3,1]) except Exception as exc:
print(str(exc))
server.stop() if __name__ == "__main__":
main()
MASTER = modbus_tcp.TcpMaster('127.0.0.1', 502)
hold_value = MASTER.execute(slave=1, function_code=cst.READ_HOLDING_REGISTERS, starting_address=0, quantity_of_x=10)
print(hold_value)

或者打开应用端:

执行后抛出异常:

Modbus Error: Exception code = 2
Modbus Error: Exception code = 2
Modbus Error: Exception code = 2
Modbus Error: Exception code = 2
Modbus Error: Exception code = 2

问题原因:

浅显分析:

slave_1.add_block('0', cst.HOLDING_REGISTERS, 0, 4)  此处相当于创建了4个设备

hold_value = MASTER.execute(slave=1, function_code=cst.READ_HOLDING_REGISTERS, starting_address=0, quantity_of_x=10)   代码中 starting_address=0, quantity_of_x=10  访问了10个设备,大于创建的设备数

Modbus Polls中访问的设备数大于创建的设备数

专业分析:

查询中接收到的数据地址不是从属服务器允许的地址。更具体地说,参考号和传输长度的组合是无效的。

总结:

访问的设备数必须小于等于创建的数量

python Modbus 进行通讯时抛出Modbus Error: Exception code = 2的相关教程结束。